It can test the functions and performance of merging units, conventional relay protection devices, digital relay protection device measurement and control devices, and intelligent terminals, and is suitable for power plants, substations, various scientifi
Response within
24 hours
Free warranty
12 month
On-line training
Support
Current voltage source output: 6 channels, each with 120V/60VA | ||
range | Every route 120V/60VA | |
Accuracy | 0.2V~2V 时,±4mV;2V~120V 时,±0.1% | |
resolving power | 1mV | |
AC current source output: 6 channels, each channel 30A/450VA, 6 parallel 180A | ||
range | 每路 30A/450VA(250VA) | |
Accuracy | 0~500mA 时,±1mA; 500mA~30A 时,±0.1% | |
resolving power | 1mA | |
phase | ||
Range | 0~360° | |
Accuracy | ±0.1° | |
resolving power | 0.1° | |
frequency | ||
Range | 0~1000Hz | |
Accuracy | <±0.001Hz(0~65Hz) <±0.01Hz(65~450Hz) <±0.02Hz(450~1000Hz) |
|
resolving power | 0.001 Hz | |
Time | ||
Range | 10ms~9999.999s | |
resolving power | 1ms | |
Switching input | ||
quantity | 8 pairs | |
Interruption capacity | DC250V /0.5A | |
Switching output | ||
quantity | 6 pairs, of which 2 pairs are fast opening (0.1ms) | |
DC voltage source output: 6 channels, each with ± 160V/60VA | ||
range | 0~160V/60VA per channel | |
Accuracy | 0.2% | |
DC current source output: 6 channels, each with ± 20A/200VA | ||
range | 0~20A/200VA per route | |
Accuracy | 0.2% |