Cable length and fault test section
- Single-ended ranging: greater than 120Km
- Sampling frequency: 160MHz, 80MHz, 40MHz, 20MHz, 10MHz, 5MHz, 2.5MHz
- Pulse amplitude: not less than 120V at 50Ω
- Pulse width: 0.2μs and 2μs
- Single-ended test blind zone of the host: less than 2m; no blind zone for double-ended testing
- Host length measurement error: 1‰~2‰
- Reading resolution: V/2f (V = wave propagation speed in cable (m/μs), f = sampling frequency (MHz)); e.g., for oil-impregnated paper cable with V=160m/μs and f=160MHz sampling, the reading resolution is 160/(2×160)=0.5m
- Three-wave comparison function
- Pre-set wave propagation speeds for 5 cable media: oil-impregnated paper: 160m/μs, cross-linked: 172m/μs, PVC: 184m/μs, non-dripping: 160m/μs, coaxial cable: 196m/μs, plus customizable media
- Automatic analysis function: automatically analyze low-voltage and high-voltage pulse test waveforms, and automatically identify whether the fault point breaks down during fault testing
- Sampling methods: normal trigger mode, full-automatic trigger mode, current sampling
Dc resistance measurement section of cable
- Measurement range: 1mΩ~2kΩ
- Output current: 0~10A, manual or automatic current selection
- Measurement accuracy: 0.2%±2 digits
- Maximum resolution: 0.1μΩ
- Automatically convert resistance to the value at standard temperature (20℃)
Other measurement functions
- Cross-sectional area measurement range: 4mm²~2500mm²
- Cross-sectional area measurement accuracy: ±2%
- Temperature measurement range: -45℃~90℃
- Temperature measurement accuracy: ±0.5℃
- Measurement duration: 0~600s
Other general technical parameters
- Power supply: AC220V 50Hz, with built-in rechargeable battery
- Charging time: 1~2 hours for full charge
- Working time: continuous operation for 8 hours
- Display: large-color LCD (sunlight screen) with Windows operating interface
- Data interface: USB
- Keys: all-metal keys, mouse
- Storage capacity: 32G
- Dimensions: 400mm×180mm×330mm
- Weight: 5KG
- Operating temperature: -10℃~50℃
- Environmental humidity: ≤90%RH, no condensation