Ultra-low frequency high voltage generator
Ultra-low frequency high voltage generator

Ultra-low frequency high voltage generator

Applications:

It is widely used in AC withstand voltage test of large capacitance equipment such as generator and cable power container.

  • Response within
    24 hours

  • Free warranty
    12 month

  • On-line training
    Support

Profile:

This product integrates digital frequency conversion technology, adopts microcomputer control, automatic voltage boost, buck, measurement and protection. Because of the electronic, so small size and light weight, large screen LCD display, clear and intuitive, and can display output waveform, print test reports.

Features:

1.The rated voltage is less than or equal to 50kV ultra-low frequency using a single link structure (a booster); The ultra-low frequency of more than 50kV adopts a series structure (two boosters in series), which greatly reduces the overall weight and enhances the load capacity, and the two boosters can be used separately for the ultra-low frequency of low voltage levels.
2. Current, voltage, waveform data are directly sampled from the high voltage side, so the data is accurate
3. With overvoltage protection function, when the output exceeds the set voltage limit value, the instrument will stop protection, the operation time is less than 20ms.
4. With overcurrent protection function: designed for double protection of high and low pressure, the high pressure side can be stopped according to the set value; When the current on the low voltage side exceeds the rated current, the shutdown protection will be carried out, and the operation time is less than 20ms.
5. The high voltage output protection resistor is designed in the booster body, so there is no need to connect another protection resistor outside.
6. Due to the use of high and low voltage closed-loop negative feedback control circuit, the output has no capacity rise effect.

Parameter:

2. Output frequency: 0.1Hz, 0.05Hz, 0.02Hz
3. Load capacity: 0.1Hz 1.1μF; 0.05Hz 2.2μF; 0.02Hz 5.5μF
4. Measurement accuracy: 3%
5. Voltage positive, negative peak error: ≤ 3%
6. Voltage waveform distortion: ≤ 5%
7. Conditions of use: indoor, outdoor; Temperature: -10℃∽+40℃; Humidity: ≤ 85%RH
8. Power safety tube: See Table 1
9. Power supply: frequency 50Hz, voltage 220V±5%.