Products

Products

KDJB-802 relay protection calibrator
KDJB-802 relay protection calibrator

KDJB-802 relay protection calibrator

Applications:

Output up to 4 phase voltage and 3 phase current, can be a variety of combinations to achieve the conventional 4 phase voltage and 3 phase current type output mode, not only compatible with the traditional various test methods, but also convenient for three-phase transformer differential test and plant power quick cutting and ready self-throwing test.

  • Response within
    24 hours

  • Free warranty
    12 month

  • On-line training
    Support

Profile:

The device is directly connected to the external laptop or desktop computer for operation, convenient and fast, stable performance.
The output end has always adhered to the use of high-fidelity, high-reliability modular linear power amplifier, rather than switching power amplifier, good performance. It will not cause high and medium frequency interference to the test site, and ensure the smooth waveform from large current to small current.

Features:

High performance host: The output part is controlled by DSP, the operation speed is fast, the real-time digital signal processing ability is strong, the transmission frequency band is wide, and the high resolution D/A conversion is controlled. The output waveform precision is high, the distortion is small and the linearity is good. A large number of advanced technology and precision components and materials are used, and professional structural design is carried out, so the device is small in size, light in weight, full in function, easy to carry, can be started to work, and flow test is very convenient.
Strong software function: can complete a variety of large and complex calibration work with high degree of automation, can easily test and scan a variety of protection set values, fault playback, real-time storage of test data, display vector graphics, online printing reports, etc. Convenient for three-phase differential protection testing.
With independent dedicated DC power output: with one 110V and 220V dedicated DC power output.
Complete interface: The device has a USB communication port, which can communicate with computers and other external devices.
Perfect self-protection function: reasonable design of heat dissipation structure, reliable and perfect hardware protection measures, with power soft start function, software for fault self-diagnosis and output lock and other functions.

Parameter:

Ac current output:
Output accuracy: 0.2
Phase current output (RMS) : 0 ~ 40A
Three parallel current output (RMS) : 0 ~ 120A
Phase current long time allowable working value (effective value) : 10A
Phase current Maximum output power: 420VA
Three parallel current maximum output power: 900VA
Allowable working time for maximum current output: 10s
Frequency range (fundamental wave) : 20 ~ 1000Hz
Harmonic frequency: 1 ~ 20 times
Dc current output
Output accuracy: 0.2
Current output: 0 ~ ±10A/phase, 0 ~ ±30A/three parallel
Maximum output load voltage: 20V
Ac voltage output
Output accuracy: 0.2
Phase voltage output (RMS) : 0 ~ 120V
Line voltage output (RMS) : 0 ~ 240V
Phase voltage/Line voltage output power: 80VA / 100VA
Frequency range (fundamental wave) : 20 ~ 1000Hz
Harmonic frequency: 1 ~ 20 times
Dc voltage output
Output accuracy: 0.2
Phase voltage output amplitude: 0 ~ ±160V
Line voltage output amplitude: 0 ~ ±320V
Phase voltage/Line voltage output power: 70VA / 140VA
Switching quantity and time measurement
Switching input: industrial control type, 10 channels; Empty contact: 1 ~ 20mA, 24V; Potential contact access: "0" : 0 ~ +6V; 1: +11 V to +250V
Switching output: industrial control type, 8 pairs; DC: 220V / 0.2A; AC: 220V / 0.5A;
Time measurement: measuring range 0.1ms ~ 9999s; Measuring accuracy 0.1ms;
Overall dimensions: 360×280×135mm³
Single weight: 13kg
Power supply: AC 220V±10%, 50/60Hz
Ambient temperature: -10℃ ~ +50℃